Excellence In Engineering Since 1949

Products Home | Cooling Equipment | Dummy Loads | Calorimeters | Hydraulic & Filtering Systems | Other Systems
Technology Info Home | Cooling Systems | Dummy Loads | Calorimeters | Formulas & Conversions
Industries & Customers Home | Industries
Sales & Support Home | Catalog | Cooling System Info. | Request Manual
Company Home | Company Facilities | Directions

RU Series - Refrigerated

small logo

RU Series Refrigerated Liquid Cooling Systems


RU series with Built-In-Circulating System Air Cooled Condenser.

Coolant may be water, glycol/water solutions, PAO, Coolanol, Fluorocarbons or other liquids. CFC free, sealed refrigeration system features high efficiency liquid-to-refrigerant heat exchanger incorporating a hot gas bypass system for close temperature control and freeze protection. A wide variety of options is available including deionizers, flow meters, flow control valves, computer interfacing and outdoor/weatherproof units.

Easy installation. Connect supply and return lines to heat load, connect line power, ground and safety interlock and fill system with coolant.

Water cooled condensing units (RUW Series) are available. They require customer supplied tap or facility water as the secondary coolant.

Applications:

  • CAT Scan
  • X-ray machines
  • MRI
  • Lasers
  • Pharmaceutical
  • Medical
  • Industrial processes
  • Holography
  • Airborne
  • Radar
  • Communications
  • Avionics
  • Electronics
  • Militray
  • Facility Chillers

  •  

    Model Amb. 70° F Capacity
    Watts Water@ 65° F
    GPM Flow
    @ 50 PSID
    RU-50
    1,600
    1.5
    RU-75
    2,400
    1.5
    RU-100
    3,200
    1.5
    RU-200
    8,000
    4.0
    RU-300
    13,500
    4.0
    RU-400
    17,500
    4.0
    RU-500
    21,500
    8.0
    RU-750
    30,000
    8.0
    RU-1000
    40,000
    10.0
    RU-1500
    60,000
    15.0
    RU-2000
    80,000
    20.0

    Performance data representative of standard units using water. Consult the factory for other flow rates, coolants (glycol, coolanol, PAO, Fluorocarbons, etc.), voltages and frequencies (50Hz, 400Hz) and larger refrigerated units. Specifications subject to change without notice.